Power projection
Power projection¶
▶ Video: Part 7 — Power projection & rebalancing
Every rack in the editor shows how much power it will draw once the design is applied — before anything is cabled. The numbers are read-only and follow every edit live: drop, move or remove a device and the bar changes on release, no Save needed. Nothing is written to DCIM.
This page covers the rack-level view: the power bar and the heatmap. Where the load lands per PDU and per breaker bank is Power distribution.
The power bar¶
Directly under each rack's name:
5600 / 11776 W · 48% ⚠ 4
- Draw — the sum of every device the rack will hold: its current devices, minus the ones this design removes or moves out, plus the ones it adds or moves in. A moved device's draw leaves one rack and arrives in the other.
- Capacity — the rack's power feeds, each counted the way NetBox counts a
feed's available power (volts × amps × phases, derated by
POWERFEED_DEFAULT_MAX_UTILIZATION). Planned feeds count exactly like real ones. A rack with no feeds at all usespower_capacity_default_w(1000 W) as a stand-in, so a greenfield rack still has a bar. - Utilization — draw / capacity. The bar turns amber at
power_warn_pct(80 %) and red atpower_critical_pct(100 %). - ⚠ N — devices with a power port that isn't cabled to anything. Hover the ⚠ for their names.
Where a device's draw comes from¶
In order: the device's own power ports (allocated_draw, or maximum_draw
if you set power_draw_basis = "maximum" — each falls back to the other when
unset), then its device type's power port templates. Two special cases:
- Unknown draw — the device has power ports but none of them carries a draw value. It counts as 0 W but is flagged (hatched in the heatmap, named in the hover), because missing data isn't the same as zero.
- Passive — no power ports at all (patch panels, cable managers, blanking panels). It draws nothing and is never flagged.
Devices whose role is in power_exclude_roles (by default pdu and
unmanageable-pdu) are power infrastructure, not load: they never count
toward draw. Give a PDU the PDU role — one planned under another role counts its
own rating as consumption and the bar goes red.
The heatmap¶
Tick Power heatmap on the toolbar. Normal tile colours are replaced by a green → red scale: each tile's colour is its draw as a share of the biggest consumer in its own rack. The heaviest device in a rack is red; one drawing half as much is amber. The scale is per rack, so the same switch can read amber in one rack and green in another that holds heavier servers. Unknown-draw devices are hatched, not green.
Configuration¶
| Key | Default | Effect |
|---|---|---|
power_capacity_default_w |
1000 |
Capacity of a rack with no feeds |
power_draw_basis |
"allocated" |
"allocated" or "maximum" draw from power ports |
power_warn_pct |
80 |
Utilization that turns the bar amber |
power_critical_pct |
100 |
Utilization that turns the bar red |
power_exclude_roles |
("pdu", "unmanageable-pdu") |
Role slugs that never count as load |
All are optional keys under PLUGINS_CONFIG["netbox_rack_design"].
Related¶
- Power distribution — per-PDU / per-bank chips, bank zones, feed binding, the three distribution modes.
- Planned racks — supply for a rack that doesn't exist yet.
- Power projection spec — the design notes behind it.