PDU distribution spec

PDU power distribution — specification

Status: active — universalization in progress (started 2026-07-17; reworked to the feed-model design 2026-07-22). Fleshes out Tier 2/3 of docs/power-projection-spec.md with the concrete distribution algorithm: how a planned device's draw is split across a rack's PDUs, feeds, and banks, and how the editor previews the resulting per-bank load.

Definition of done = the conformance checklist (§10) covered by backend tests (mirrors naming.py's test-first rule) and the heatmap items verified live.

0. Principle — universal base, native-first

The distribution engine is the power analogue of the naming-through-script engine (naming.py), but with one deliberate difference from the naming engine: there is a working built-in. Two site-agnostic naming conventions (§1) make it safe to compute a real distribution with zero config and zero script, so the plugin can announce power distribution as a base feature — not only as a bring-your-own-script hook.

0.1 The three tiers

Tier Who it's for Mechanism
"none" racks/sites with no per-bank accounting No bank attribution at all — where a device sits is irrelevant because there is no way to know which bank feeds it. The heatmap falls back to a per-device share of the rack total.
"builtin" (announced) anyone who follows the two naming conventions Purely native: bank from the outlet port name, breaker from the bound feed, feed-leg from the binding, rack units split symmetrically across banks in a fixed direction. Reads no custom fields at all — no rack ceiling, no PDU orientation.
"script" sites whose distribution logic differs A dotted path to fn(rack, devices) -> Distribution. This is where distribution logic lives — the conventions of a company or a data centre — and the only tier where custom fields reach the engine, via the planning_fields config bridge (merged over rack.cf for this tier only). On any failure the engine logs a warning and returns None; the heatmap degrades to the per-device view and never breaks the editor.

0.2 The universal split — native vs config

  • Everything native is base logic, never config. Real PowerFeed voltage/amperage/phase/supply, port allocated_draw, the outlet port name, the device name — the plugin reads these directly. They exist on every NetBox instance, so no mapping is needed.
  • The builtin tier is purely native — it reads no custom fields at all. Bank identity, breaker sizing, and the unit→bank split direction all come from outlet names and feed bindings; there is no rack-ceiling lookup and no PDU-orientation lookup in "builtin". Custom fields matter only once a site needs behaviour the two conventions can't express.
  • Config bridges custom fields only, and only for the script tier. Site quirks that live in custom fields — power_limitation (rack ceiling: the PDUs may total more breaker capacity than the hall can cool, so the cap is a separate fact that must alarm independently), pdu_location (which end of the rack a PDU's tail/inlet faces, so a script knows where each bank physically sits), and any future field — are declared in planning_fields and reached by a distribution_script through its source key, so the plugin never hardcodes a site's cf names in the code it ships. A DC that doesn't run a script simply doesn't declare them; the dialog shows nothing extra and the base feature still works.

0.3 The two universal conventions

The base feature works out of the box iff the data follows these two rules — they are the documented contract for using the plugin, replacing the old "bank identity is site-specific, so no built-in" stance:

  1. Bank = first segment of the outlet port name. A PDU outlet is named "<bank>/<port>"; the segment before / is the bank (1/1 → bank 1). The count of distinct bank ids across a PDU's outlets is its power_bank_count.
  2. Feed-leg = the feed a PDU is bound to (§6). A PDU is on leg A because it is bound to Feed A, not because of its name. Redundancy (a device's two PSUs on two feeds) falls out of the bindings. There is no device-name parsing in the base.

Everything here is a read-only overlay: no dcim writes, no design dirty flag, nothing saved back to real records. A bad script degrades to the crude rack total — it must never break the editor.

1. Vocabulary (from the NetBox power model)

  • PDU — a device with role slug in {pdu, unmanageable-pdu}, status active/planned. It distributes power; it is not a consumer (excluded from the draw sum via power_exclude_roles).
  • Feed — the power source a PDU draws from. Two kinds, one shape:
  • Real — a native dcim.PowerFeed the PDU's power port is cabled to (provisioned racks). Carries voltage, amperage, phase, supply.
  • Planned — a plugin-side DesignPowerFeed (§6) for greenfield planning, where the rack has no real feeds yet. Same electrical fields.
  • Feed-leg (a / b) — the redundancy leg = which feed the PDU is bound to. Two independent feeds; a rack is sized so either leg can carry the whole load alone on failover.
  • Bank — a breaker/phase group inside one PDU. Identity lives in the outlet PORT name ("<bank>/<port>", §0.3), not on the PDU. power_bank_count = distinct <bank> values across a PDU's outlets.
  • Breaker (per bank)bank_max = pdu_input_draw / power_bank_count. A bank whose charged load exceeds this is an overload (alarm).
  • PDU input capacity (allocated_draw) — from the bound feed: voltage × amperage × phase_rate, phase_rate = 1.732 for three-phase else 1. For a real PDU with no binding and a cabled PowerFeed, the native cable path supplies the same figure; with neither, the port's own allocated_draw.
  • Phase — from the bound feed's phase (3-phase → phase_rate = 1.732).

2. Distribution algorithm (built-in + reference script share it)

The base builder (distribution.build_native) and the shipped reference script (distribution_example.py, cf. naming_example.py) run the same algorithm over the same helpers — the script only exists so a site can override the behaviour pieces (direction, ceilings, PSU scheme). Two independent questions, resolved per rack.

2.1 Which bank owns each rack unit — unit → (pdu, bank) map

_get_pdu_dicts(). For each feed-leg (a, b), a map from every rack unit to the PDU+bank feeding it — so an uncabled device is still attributed by its U position.

units          = [1 .. rack.u_height]          # reversed if direction == "top"
bank_count/rack = Σ(power_bank_count over PDUs) / 2      # /2 because a & b mirror
units_per_bank  = round(len(units) / bank_count/rack)

Walking PDUs in feed order, each bank claims the next contiguous units_per_bank slice of its leg's unit list. Remainder units attach to the previous bank, so every unit is owned. The builtin always splits in a fixed direction (bank 1 at the bottom) — it consults no custom field at all. A script variant (e.g. distribution_example.py) may instead read the rack custom field pdu_location (top/bottom — which end of the rack the PDU's tail/inlet faces) through the planning_fields config bridge and flip the direction so bank 1 sits where the PDU physically starts; there, pdu_location is optional: absent, direction defaults to bottom.

PDU scheme — the multiset of per-PDU bank counts, sorted and _-joined, is looked up in BANK_LIST_TO_PDU_SCHEMAS to label the topology (validation aid; unknown signature raises in the reference — the built-in tolerates it).

2.2 How much draw each device puts on which bank

Per planned device (check_power_consumption()):

  1. Skip non-consumers — roles {cable-management, patch-panel, pdu, unmanageable-pdu, rack-mount-boxes, rack-mount-kit}; a blade-server with no bank connection.
  2. Per power port, read allocated_draw. Then:
  3. Cabled (PowerPort → PowerOutlet on a PDU in this rack): bank from the outlet name "<bank>/<port>", PDU/leg from the binding → charge to that PDU+bank.
  4. Uncabled (planned) — and a device whose cabling leads OUT of this rack: look up the device's U position in the §2.1 map for each leg → charge there. A device MOVED here still carries its cabling to the source rack's PDU until the design is implemented, so that cabling names a PDU this topology does not contain; treating it as uncabled is what makes the draw follow the device across racks instead of disappearing from both.
  5. Active vs planned split — status planned charges planned_power; else allocated_power. Both accumulate per bank (committed vs projected).
  6. Redundancy is "full", never split — a device's draw is charged in full to each feed-leg it participates in (on an A/B failure the surviving leg carries the whole load). A single-PSU device sits entirely on one leg.

2.3 Per-PSU → leg wiring

For a planned/uncabled device, which PSU lands on which leg is a small scheme table (pdu-1 = leg a, pdu-2 = leg b): p2 → ps1→a, ps2→b; p4 → ps1,2→a, ps3,4→b; p6 → ps1-3→a, ps4-6→b; single PSU → the leg with more free ports. Redundancy sanity checks warn, don't block. This is a behaviour piece — script-only; the built-in uses a simple A/B split.

3. Data contract — the Distribution object

Structured, template-agnostic, attached to the projection bundle as power["distribution"]. Single source for the editor heatmap and any read-only view.

Distribution
  scheme            "2x1PH2Banks" | ...            # §2.1 topology label
  pdu_location      "top" | "bottom"
  pdus:  { pdu_name: {
            feed_name:        "a1",
            feed_letter:      "a" | "b",           # = the bound feed's leg
            feed_source:      "real" | "planned",  # which kind of feed backed it
            phase:            1 | 3,
            allocated_draw:   int  W                # PDU input breaker (bound feed)
            power_bank_count: int,
            banks: { bank_id: {
                       max_power:       int W       # per-bank breaker
                       allocated_power: int W       # committed (active devices)
                       planned_power:   int W       # projected (planned devices)
                       util_pct:        float
                       state:           ok|warn|critical|overload
                       units:           [int, ...]
                       devices:         [ {name, ru, draw_w, status, ports}, ... ]
            } }
  } }
  rack:  { power_limitation_w, power_consumption_w, alarm: bool, warnings: [str] }

state uses the existing thresholds (power_warn_pct, power_critical_pct); allocated_power > max_power is overload → sets rack.alarm + a warning.

4. Heatmap behavior — what distribution_mode changes

The heatmap toggle is unchanged; distribution_mode decides what the colors mean when it's on.

  • "none" — per-device rack-share gradient (today's Tier-1 behavior). PDUs are excluded infrastructure.
  • "builtin" / "script" — the plugin colors from the returned Distribution; the PDU/bank becomes the heat subject:
  • each bank is a filled health bar green→red by (allocated_power + planned_power) / max_power; overload is a distinct hard-red.
  • PDU column headers are feed-leg colored (leg a / leg b) — that is the A/B key (no separate legend). Banks of one PDU stack vertically.
  • consumer tiles get an A/B feed edge by the leg(s) they land on; unknown-draw keeps the neutral hatched shade (absence of data ≠ zero).
  • instant per-bank tooltip (used W / breaker W); overload/redundancy warnings from Distribution.rack.

Toggle off → styling restores exactly (pure view state, never persisted).

5. Config

# --- Power distribution engine (see pdu-distribution-spec.md) --------------
# How per-PDU/bank load is distributed for the power heatmap.
#   "none"    -> Tier 1: per-rack total only, per-device gradient (default)
#   "builtin" -> native distribution from the two conventions (§0.3), no script
#   "script"  -> a dotted path to fn(rack, devices) -> Distribution
"distribution_mode": "none",
# Dotted path to a callable used when distribution_mode == "script".
"distribution_script": "",
# Custom-field bridge for the planning dialogs -- meaningful only when
# distribution_mode == "script" (the builtin tier reads no custom fields, so
# it ignores this entirely). Maps site custom fields into the rack/PDU
# planning inputs and into the script's view of the rack -- NATIVE fields are
# never listed here. Empty by default (the builtin feature needs none). Both
# "rack" and "pdu" keys are optional; each is a list of
# {key,label,type,source,choices?}. Example:
#   "planning_fields": {
#     "rack": [
#       {"key": "power_limitation", "label": "Power limitation (W)",
#        "type": "number", "source": "cf.power_limitation"},
#       {"key": "pdu_location", "label": "PDU location", "type": "choice",
#        "choices": ["top", "bottom"], "source": "cf.pdu_location"},
#     ],
#     "pdu": [
#       {"key": "cooling_mode", "label": "Cooling mode",
#        "type": "choice", "choices": ["active", "passive"],
#        "source": "cf.cooling_mode"},
#     ],
#   }
"planning_fields": {},

source is a dotted path (cf.<name> for custom fields, rack.role.name for a native attribute to read from a copy source) — the same token grammar as the naming templates, so it's self-documenting. It seeds the dialog / copy-from-rack; it is never written back to a native field (the planned object has no real record). type{number, text, choice}; choices for choice.

source is meaningful to scripts only — the builtin tier never resolves a planning_fields entry, so with distribution_mode at "none" or "builtin" the map has nothing to feed. Consequently the rack/PDU planning dialogs' manual cf inputs are a script-tier feature: they only surface entries once a distribution_script (and a matching planning_fields declaration) are configured to consume them.

There is no naming_template-style middle mode: distribution can't be a format string, so it's off (none), built-in (builtin), or fully delegated (script).

6. The feed model — how a PDU gets its breaker

A real PDU reads its breaker from a cabled PowerFeed (native). A planned PDU has none, so instead of inventing a parallel shape (inline V/A/phase JSON) the plugin mirrors the native model: model the feed, and bind the PDU to it. The read path is then uniform — real or planned, "get the bound feed, read its electricals" — so the script/built-in never branches on real-vs-planned.

6.1 DesignPowerFeed (planned feed)

One row per planned feed, scoped to (design, rack):

DesignPowerFeed
  design      FK Design      (CASCADE, related_name="planned_feeds")
  rack        FK dcim.Rack   (CASCADE)
  name        str            # e.g. "Feed A" — its leg/identity
  voltage     int
  amperage    int
  phase       1 | 3
  supply      "ac" | "dc"
  unique_together (design, rack, name)

A NetBoxModel (unlike HiddenDesignRack/DesignRackPower, which stay plain): a planned feed is design data a team reads, edits and deletes on its own. Read-only w.r.t. dcim — no real PowerFeed is ever written.

Its own views (Unreleased). Feeds were created by the editor's dialogs and then visible nowhere, with no way to remove one — while still sizing a greenfield rack's capacity bar, so a stray feed silently inflated it. They now have the same view set as DesignPlacement:

Route Does
Rack Design → Planned Power Feeds (/plugins/rack-design/power-feeds/) filterable list, bulk edit, bulk delete, import/export
/power-feeds/<pk>/ detail: identity, electricals, derated capacity, and the planned PDUs bound to it
/power-feeds/<pk>/edit/ · /delete/ correct or remove one feed
the design page's Planned power feeds panel per-row edit + delete, returning to the design
/api/plugins/rack-design/planned-power-feeds/ · GraphQL planned_power_feed the REST/GraphQL twins

DesignPowerFeed.derated_watts is the figure the capacity bar actually uses — breaker_watts() derated by the instance's POWERFEED_DEFAULT_MAX_UTILIZATION — so the list, the detail page and the rack's chips can never disagree about what a feed is worth. Deleting a feed unbinds the planned PDUs that pointed at it (SET_NULL), which the detail page names before you delete.

Design chains widen what counts (see Design chains). A rack's capacity figure (projection._rack_capacity_w) sums not only this design's own DesignPowerFeed rows but every APPROVED ancestor's, resolved through the same all-or-nothing resolve_baseline_chain() the placement replay uses — a non-approved or implemented ancestor contributes nothing (and the refusal is reported once, by the projection's conflicts, not duplicated here). See docs/design-chains.md.

Two nullable FKs on DesignPlacement (avoids a GenericForeignKey; both queryable):

DesignPlacement
  real_power_feed     FK dcim.PowerFeed        (null, on_delete=SET_NULL)
  planned_power_feed  FK DesignPowerFeed       (null, on_delete=SET_NULL)
  • clean() enforces at most one is set.
  • property bound_feed returns whichever is set, exposing a duck-typed {voltage, amperage, phase, supply, name} regardless of source.
  • One PDU binds to one feed (matches "one power port → one feed").
  • A PDU may bind to an APPROVED ancestor's planned feed, not only to a real feed or one this design defined itself (DesignPlacement. _validate_planned_power_feed accepts this design or any design in its baseline_chain()) — the same rule that lets a placement act on an ancestor's planned add (base_placement). See docs/design-chains.md.
  • A PDU's custom fields come from one of two sources, mutually exclusive:
  • Live from a real device — new FK power_source_device (see §6.5);
  • Manual entry — via power_config (see §6.5).

6.3 Dialog flows

Common case — rack has real feeds (ordered against a contract → PowerFeeds + power_limitation already exist). Adding a PDU opens the bind-to-feed dialog:

  • a picker of the rack's feeds — real feeds first, then any planned feeds;
  • a secondary "+ define planned feed" option, always available as a fallback (so a mixed real/planned rack is never a dead end);
  • confirm → the binding (real_power_feed_id or planned_power_feed_id) is stashed on the widget and rides the design Save.

Edge case — rack has no feeds (greenfield). The per-rack Power button (gated: shown when the rack has no real feeds) opens the planned-power flow:

  • define planned feeds (DesignPowerFeed) — manual (name + V/A/phase/supply) or copy-from-rack (materialize another rack's real feeds);
  • set the planned power_limitation (and any planning_fields cf) via DesignRackPower;
  • then adding PDUs binds to those planned feeds.

Copy from rack REPLACES the target's planned feeds (ruled 2026-08-28). The button's promise is "this rack is fed like that one", so afterwards the target holds exactly the source's set — no more, no less. It used to upsert by name and only ever add, and since retargeting rewrites a rack-name prefix only, feeds named by any other scheme (Utility A) never collided: copying from three racks in turn left the union of all three, and the rack's capacity bar read as the sum of every source ever clicked. Rules that fall out of it:

  • a feed whose (retargeted) name survives keeps its row, so every PDU bound to it stays bound; the rest are deleted and their PDUs unbound (planned_power_feed is SET_NULL), with the count returned so the dialog can say so;
  • a source with no feeds is a no-op, not a wipe — picking the wrong rack in the dropdown must not strip a supply that has no undo.

Planned feeds are visible and removable. They size a greenfield rack's capacity bar, so they cannot be write-only:

  • the rack power dialog lists this rack's planned feeds, each with a × that deletes it (DELETE .../planned-feed/), reporting how many PDUs it unbound;
  • the design detail page carries a Planned power feeds panel — every feed in the design, its rack, its electricals, the derated watts the bar actually uses, and the PDUs bound to it.

A failing engine must SAY SO (ruled 2026-08-28). generate_distribution() degrades to None on any failure, and an empty chip strip is indistinguishable from a rack that legitimately has no PDUs — four causes, one blank result. So the projection now carries a status beside the distribution, and the editor renders it under the power bar:

state meaning shown as
ok a distribution was produced nothing (the chips speak)
off distribution_mode is none muted "Per-bank distribution is off"
failed the engine raised red notice; hover gives the exception type, its message and the script's dotted path
empty the engine ran, resolved no PDU muted notice; hover names each omitted PDU and why (no feed / no parseable outlet banks)

generate_distribution_status(elevation) returns (distribution, status); generate_distribution(elevation) still returns just the distribution for scripts and older callers. The status rides elevation.power["distribution_status"], the rd-diststatus-<rack_id> json_script, and the distribution_status block of recompute-distribution/ — so a live edit that breaks the engine reports itself immediately rather than at the next page load. Degrading (never erroring the page) is unchanged; what changed is that the degrade is visible.

Feeds are never defined by a script — a script can't invent breaker amperage; it needs source data, which the model provides. The script/CF layer is for distribution behaviour only.

6.4 DesignRackPower (rack custom-field override)

Unchanged in shape/purpose: one row per (design, rack), holding the planned custom_fields (e.g. power_limitation, pdu_location) merged in-memory over rack.cf before the distribution runs (never written to dcim.Rack). This merge only matters for distribution_mode = "script" — a distribution_script reads it through the planning_fields config bridge; the builtin tier ignores rack.cf entirely. Now populated via the planning_fields-driven rack dialog.

Design chains merge oldest-first (see Design chains). DesignRackPower.effective_custom_fields(design, rack) resolves the merge a distribution_script actually reads: every APPROVED ancestor's override for this rack, oldest first, then this design's own row last — so a nearer override wins over a farther one, and this design's own value always wins over anything inherited. Uses the same resolve_baseline_chain() all-or- nothing rule as everything else in the chain; a refused ancestor contributes nothing from its layer but never erases this design's own override. See docs/design-chains.md.

6.5 Planned-PDU custom fields — device reference vs manual entry

A planned PDU's custom fields are resolved from one source only (mutually exclusive):

6.5.1 Live device reference — power_source_device FK
DesignPlacement
  power_source_device  FK dcim.Device  (null, on_delete=SET_NULL)

When set, the PDU's cf are read live from the source devicedevice.cf (the full custom-field value dict) — on every generate_distribution() call, never snapshotted. Editing the source device's cf updates the plan immediately.

  • clean() enforces power_source_device and manual power_config are never both supplied.
  • The source device can be any dcim.Device (not restricted to PDU role); site convention decides (e.g., a PDU template device, a real PDU, etc.).
  • Unresolvable source (device deleted) degrades cleanly: logged, fallback to manual power_config.
6.5.2 Manual entry — power_config custom fields only

power_config is now a JSON field holding:

{"custom_fields": {...}}

The custom_fields map is populated at planning time via the planning_fields["pdu"] config schema (same cf-bridge grammar as planning_fields["rack"], §5), drives the PDU dialog's cf inputs, and persists to power_config on Save. The old feed key and copied_from/source provenance are gone — feed data now lives on the feed model / binding (§6.1–6.2).

6.5.3 Distribution engine resolution

generate_distribution() resolves a PDU's custom fields as follows:

  1. If power_source_device is set, read device.cf live (and log source);
  2. else if power_config.custom_fields exists, use it;
  3. else use {} (no custom fields).

This happens per-rack, per-PDU; the distribution object (Distribution.pdus[pdu_name]) carries no provenance marker — to the heatmap and read-only views, the cf are resolved and uniform.

7. What the engine receives & returns

7.1 Inputs (the planned world, read-only)

generate_distribution(elevation, *, mode=None) builds, per rack:

  • rack — the planned dcim.Rack; the built-in/script reads rack.u_height, rack.cf (the cf value dict — not .custom_fields, a manager), and rack.devices.all() for real PDUs. Effective cf = real rack.cf merged with DesignRackPower (§6.4).
  • devices (devices_from_elevation) — planned consumers plus planned PDU adds. Each PDU entry carries:
  • role = pdu, device = None (planned) or the real device;
  • device_type (for PowerOutletTemplates → power_bank_count);
  • a resolved feed dict from the binding (bound_feed → real or planned, §6.2) — uniform {voltage, amperage, phase, supply, name, leg, source};
  • custom_fields — resolved per §6.5.3 (from power_source_device.cf live, or fallback to manual power_config.custom_fields, or {}). Consumers carry identity, u_position/face, draw_w/draw_known, and power_ports (each allocated_draw + outlet peer where cabled).

The engine never queries dcim for writes and never mutates its inputs.

7.2 Resolution & fallback (distribution.py)

Import-safe, read-only, parallel to naming.py:

DEFAULT_DISTRIBUTION_MODE = "none"
generate_distribution(elevation, *, mode=None) -> Distribution | None
    "none"    -> None                        # caller uses Tier 1
    "builtin" -> build_native(rack, devices) # the two conventions (§0.3)
    "script"  -> _run_script(...), guarded → None on any failure
_run_script -> import_string(distribution_script)(rack, devices)

An empty/unimportable/non-callable path, or any exception the script raises, is caught → logs a warning → returns None → page falls back to the none heatmap. A buggy script degrades the overlay; it never errors the editor. Same SCRIPTS_ROOT story as naming (the script may live in scripts/, editable from the NetBox UI).

7.3 What the plugin does with the result

projection.project_rack calls generate_distribution(elevation) while building the power bundle and attaches the Distribution (or omits on None) as power["distribution"], computed server-side so editor and read-only elevation read identical figures.

Recompute cadence in the editor is live: the per-bank chip strip refreshes on every add/remove/move, like the always-live power bar. Because bank assignment is server logic (real cabling / a custom distribution_script) the browser must not duplicate, the editor re-runs the SAME engine over the unsaved layout via the read-only recompute-distribution endpoint (§8) — it applies the posted layout through the save-layout reconciliation inside a rolled-back transaction, so the engine sees the live edit but nothing is persisted. First paint (and the read-only elevation, which has no editor) uses the static server-rendered figure.

8. API endpoints

All authenticated, read-only w.r.t. dcim, with debug logging on entry + result.

  • GET .../designs/{id}/feeds/?rack_id= → the rack's real PowerFeeds (uniform electricals) + its DesignPowerFeeds, for the bind picker (real first).
  • POST/GET .../designs/{id}/planned-feed/ → upsert / list DesignPowerFeed (create a planned feed; copy-from-rack materializes real feeds).
  • POST/GET .../designs/{id}/rack-power/ {rack_id, power_config} → upsert / read DesignRackPower (planned power_limitation etc.), immediate.
  • GET .../power-source/?kind=rack&rack_id= → copy-from-rack prefill: the rack's custom fields, read via the planning_fields["rack"] source paths (for rack dialog prefill and copy operations).
  • POST .../designs/{id}/recompute-distribution/ (body = the save-layout payload) → the fresh per-rack Distribution for the UNSAVED editor layout, {"distributions": {"<rack_id>": <Distribution-or-null>}}. Applies the layout through the save-layout reconciliation inside a rolled-back transaction and projects each rack, so it re-runs the real distribution engine live yet persists nothing. Requires only view on the design. Drives the editor's live per-bank chip refresh (§7.3).
  • PDU listing — the PDU dialog lists a rack's PDUs via the core dcim API (GET /api/dcim/devices/?rack_id=<id>&role=pdu&role=unmanageable-pdu), not a plugin endpoint. Enables referencing existing PDU devices for the power_source_device FK.
  • Save-layout item carries:
  • real_power_feed_id / planned_power_feed_id (the feed binding)
  • power_source_device_id (the cf source device, if set)
  • power_config (manual cf as {"custom_fields": {...}}, if set) All written by _reconcile_item on PDU adds; the binding and cf source ride the existing Save.

9. Frontend instrumentation (debuggability)

Every interaction that touches this feature emits a dev-only tracer event (window.__rdDragTrace, gated on DEBUG/DjDT — inert in prod), carrying its actual payload, not just a name:

  • device move/drag → source/target unit, device, which PDU banks it now charges, draw delta;
  • every button press → which button + rack/PDU context + state;
  • copy-from-rack → source rack, feeds/cf values pulled, what got prefilled;
  • bind-to-feed → chosen feed (real/planned, id, V/A/phase, leg) + the PDU;
  • planned-feed create → the full feed record;
  • dialogs → open / confirm / cancel with field values;
  • save → the binding + planning payload per item;
  • heatmap renderheat.feed / heat.bank per bank (load/breaker/leg).

Backend mirrors this with a logger.debug sweep across feed resolution (real vs planned), bank/leg, breaker, override applied, and every graceful fallback.

10. Conformance checklist (definition of done)

Base (builtin) — the announced feature: - [ ] distribution_mode = "builtin" with convention-named outlets + PDUs bound to feeds produces a per-bank heatmap with no config and no script. - [ ] Bank = first segment of the outlet port name (1/1 → bank 1); power_bank_count = distinct banks. - [ ] Feed-leg comes from the binding (bound feed), not device-name parsing; redundancy falls out of two bindings. - [ ] Per-bank max_power = pdu_input_draw / bank_count; allocated > maxoverload + rack alarm + warning; active vs planned tracked separately. - [ ] distribution_mode = "none" (default) reproduces today's per-device rack-share heatmap.

Feed model & binding: - [ ] A real PDU cabled to a PowerFeed sizes its breaker from that feed (native). - [ ] A planned PDU bound to a real PowerFeed sizes from it. - [ ] A planned PDU bound to a DesignPowerFeed sizes from it. - [ ] DesignPlacement.clean() rejects both FKs set; bound_feed resolves the set one; unbound PDU degrades cleanly (logged, omitted, page fine). - [ ] DesignPowerFeed round-trips; unique_together(design, rack, name); cascade on design delete.

Config bridge (script tier only) — custom fields only: - [ ] distribution_mode = "builtin" never resolves planning_fields and never reads rack.cf; only distribution_mode = "script" does. - [ ] Rack/PDU planning dialogs render their cf inputs from planning_fields; no cf name is hardcoded in JS/HTML, and the dialogs' manual cf inputs only apply when a script is configured to consume them. - [ ] planning_fields includes both "rack" and "pdu" keys (both optional); "pdu" drives the PDU dialog's manual cf inputs. - [ ] power_limitation / pdu_location reach a distribution_script via DesignRackPower merged over rack.cf, without writing dcim.Rack. - [ ] planning_fields = {} (default) → dialogs show only native inputs; base feature unaffected.

Planned-PDU custom fields (§6.5): - [ ] A planned PDU can reference a real device via power_source_device FK; its cf are read live (never snapshotted) on each distribution run. - [ ] A planned PDU can have manual cf via power_config = {"custom_fields": {...}}, driven by planning_fields["pdu"] dialog inputs (the old feed key and copied_from/source provenance are gone). - [ ] DesignPlacement.clean() rejects both power_source_device and manual power_config supplied together (mutually exclusive). - [ ] Distribution engine (§6.5.3) resolves cf in order: live from power_source_device.cf, else manual power_config.custom_fields, else {}. - [ ] Unresolvable power_source_device (device deleted) degrades cleanly; no errors, logged, fallback to manual cf.

Script (Tier 3): - [ ] distribution_example.py runs the §2 algorithm over the shared helpers and works under the builtin conventions with no site code. - [ ] Empty/unimportable/non-callable/raising distribution_scriptgenerate_distribution returns None, page falls back to none. - [ ] Nothing site-specific ships in the public wheel.

Frontend & instrumentation: - [ ] Heatmap (builtin/script): banks are filled health bars, PDU headers feed-leg colored, tiles get A/B edges, instant tooltip — verified live. - [ ] Heatmap off: original rendering restored (verified live + e2e). - [ ] Every §9 interaction emits its tracer event with the actual payload (DEBUG on); inert in prod. - [ ] Read-only throughout: no dcim writes, no design dirty flag.

11. Out of scope (v1)

  • Breaker-trip / inrush / power-factor modeling beyond NetBox's fields.
  • Auto-cabling planned devices in dcim (this feature is preview-only and never writes cable connections).
  • Writing planning inputs back to native dcim fields (the plugin only ever stores its own planning copy).