Power distribution

Power distribution

The plugin computes how each planned device's power draw distributes across the rack's PDUs, feeds, and banks for a per-bank power heatmap. The projection reads existing dcim data (real PDUs, feeds, device draws) and remains read-only — your NetBox records are never modified. The heatmap overlay shows load per bank (colored health bar), feed-leg redundancy (header colors), and overload warnings.

Configuration

All settings live in PLUGINS_CONFIG:

PLUGINS_CONFIG = {
    "netbox_rack_design": {
        # one of: "none" (default), "builtin", "script"
        "distribution_mode": "none",

        # dotted path to a callable, used when distribution_mode == "script"
        "distribution_script": "",

        # Custom-field bridge for planning dialogs (optional; empty by default)
        "planning_fields": {},
    },
}

Mode: none (default)

▶ Video: Part 12 — Bank distribution: none, builtin, script

Per-device rack-share gradient — the current behavior. PDUs are excluded infrastructure. The heatmap colors each tile by the device's share of total rack power.

Mode: builtin

▶ Video: Part 12 — Bank distribution: none, builtin, script

Zero-configuration distribution across PDUs and banks, built on two universal naming conventions that work on any NetBox instance:

"distribution_mode": "builtin",

The two universal conventions

The built-in mode works without a script or custom config, iff:

  1. Bank = first segment of the outlet port name. A PDU outlet is named "<bank>/<port>"; the part before / is the bank ID (1/1 → bank 1, 2/3 → bank 2). This is how NetBox's native outlet naming works — no custom parsing.

  2. Feed-leg = the feed a PDU is bound to. A PDU draws from one feed (real dcim.PowerFeed or planned DesignPowerFeed); the feed's identity determines the redundancy leg (A or B), never the PDU's device name. Binding is explicit — you choose which feed each planned PDU uses when you add it to the rack.

Under these conventions, the plugin distributes each device's load per bank:

  • A device the design moves (a planned add, or an existing device dragged to a new position) → charged by its new U position, regardless of any cabling it still carries. Moving a device in a design means its cable will be re-run when the design is implemented, so the old outlet doesn't say where the power will actually come from.
  • A device the design leaves in place → charged to its real outlet's bank, even if that bank doesn't match what the device's U position would suggest. Real cabling is ground truth for anything nobody is touching.
  • Redundant devices (2+ PSUs) charge both feed-legs in full (worst-case failover), whichever rule above assigned their bank.

Per-bank breaker = pdu_input_draw / power_bank_count (where power_bank_count is the distinct bank IDs on that PDU).

"builtin" reads no custom fields at all — no rack power ceiling, no PDU orientation — and always splits rack units across banks symmetrically in a fixed direction. Sites that need either of those need distribution_mode = "script" (below).

Mode: script

▶ Video: Part 12 — Bank distribution: none, builtin, script

For distribution behavior a configuration cannot express, point distribution_script at any importable callable with the signature fn(rack, devices) -> Distribution | None. The callable receives the planned dcim.Rack and the list of planned consumers + PDUs, and returns a distribution dict (see pdu-distribution-spec.md §3 for the full schema), or None when the rack has no PDUs to distribute across (heatmap stays per-device).

It runs inside the NetBox process with full ORM read access — by convention, read-only: compute a structure, never write to dcim.

Ready-to-run example (ships with the plugin)

The plugin ships a stock-runnable minimal example that reproduces the built-in distribution verbatim under the two conventions, with no site-specific data or custom field names:

"distribution_mode": "script",
"distribution_script": "netbox_rack_design.distribution_example.build",

It is a copyable template: enable it as-is to see the distribution in action, then copy and edit for your site's behavior customization (direction, breaker ceilings, PSU redundancy schemes). Like the naming example, it reads custom fields generically via the planning_fields config bridge (§ Planning fields below) — no site-specific cf names are hardcoded in the shipped code.

Fully-worked example

The plugin also ships a richer reference that fills in three customization surfaces the minimal example leaves stubbed:

"distribution_mode": "script",
"distribution_script": "netbox_rack_design.distribution_advanced_example.build",
# Optional: override the bank health-bar thresholds
"power_warn_pct": 75,
"power_critical_pct": 95,
"planning_fields": {
    "rack": [
        {"key": "power_limitation", "label": "Power limitation (W)",
         "type": "number", "source": "cf.power_limitation"},
        {"key": "pdu_location", "label": "PDU location", "type": "choice",
         "choices": ["top", "bottom"], "source": "cf.pdu_location"},
    ],
    "pdu": [
        {"key": "pdu_scheme", "label": "PDU topology label",
         "type": "text", "source": "cf.pdu_scheme"},
    ],
},

It demonstrates:

  • Topology scheme label — computes a human-readable topology string (e.g., "2x1PH2Banks") from the per-PDU bank-count signature, and allows a per-PDU override via a custom field.
  • Config-driven thresholds — reads bank utilization thresholds (power_warn_pct / power_critical_pct) from plugin config, matching the naming engine's pattern, instead of hardcoding constants.
  • Per-PDU custom field — reads the planning_fields["pdu"] config to show how a site can layer in PDU-specific planning data via the config bridge.

Both examples share the same core algorithm and helper functions with the built-in — you are not re-implementing distribution; you are customizing behaviour (direction, ceilings, scheme labels) by reading data through the config bridge. Start from distribution_example.py and adapt it to your needs.

Notes

  • Robust to misconfiguration. If distribution_script can't be resolved (wrong or empty dotted path, module not importable, target not callable) — or the script raises while computing a distribution — the engine logs a warning and falls back to the none heatmap (per-device gradient). A broken or not-yet-loaded script therefore degrades the overlay gracefully rather than blocking the editor. Fix distribution_script to restore custom distribution.
  • The structure the script returns remains read-only — the heatmap reads it, never writes. No dcim mutations, no design dirty flag.
  • rack.pk is always set (a distribution runs on a saved rack). A script never receives a preview rack.

Feed binding & planned PDUs

▶ Video: Part 10 — Greenfield planned power · Part 11 — Copying power, PDUs that bind themselves

A real PDU cabled to a real dcim.PowerFeed sizes its breaker from that feed electricals (voltage × amperage × phase, the native path). A planned PDU (a placement add, not yet realized in dcim) has no real feed yet, so the plugin models planned feeds the same way: a DesignPowerFeed row carries the same electrical fields (voltage, amperage, phase, supply), and a planned PDU binds to it just like a real PDU binds to a real feed.

Automatic binding

A PDU added to a rack that already has feeds binds itself — no dialog, no clicking. The rack usually leaves no real choice to make, and a template stamped across ten racks would otherwise mean twenty trips through the picker.

The feed is chosen by:

  1. The leg letter in the PDU's name. A PDU named ams1-pdu-r3-a1 takes the feed whose name ends in -A; …-b1 takes -B. The separator matters — a name that merely happens to end in a letter is not read as a leg.
  2. The first feed no other PDU in that rack has taken, when the name carries no leg letter. Two PDUs dropped in a row therefore land on two different feeds rather than doubling up on one.

Real feeds rank above the design's own planned feeds, which rank above feeds inherited from an ancestor design. A leg-letter match beats that ranking: a redundant second PDU on leg A is a deliberate choice, not a mistake.

The ⚡ button on the tile lights up and its tooltip names the feed ("PDU power — bound to R1-A (click to change)"), so any automatic choice is one click from being overridden.

Dialog flows

When automatic binding has nothing to pick, you get the manual flows:

  • If the rack has real feeds (a provisioned rack with dcim.PowerFeed records) — the bind-to-feed picker lists the rack's feeds (real first, then any planned feeds you've defined). Pick one to bind the PDU. This is also what the ⚡ button reopens for any PDU, bound or not.
  • If the rack has no real feeds (greenfield planning) — a per-rack Power button opens the planned-power flow where you define feeds manually (name, voltage, amperage, phase) or copy them from another rack's real feeds. The picker opens by itself right after the drop, since there is nothing to bind to yet.

A template stamp never opens a dialog at all: every PDU it carries either binds automatically or stays unbound for you to settle with the ⚡ button.

After feeds are defined, each PDU binding travels with the design and is restored on load. A PDU with no binding is omitted from the distribution (logged, no error).

A planned PDU's custom fields — e.g., pdu_scheme (a site-specific topology label; used by a distribution_script, not by "builtin") — come from one source:

  • Live device reference — if you link the PDU to an existing real device via power_source_device, its custom fields are read live on every heatmap render. Edit the source device's fields and the heatmap updates immediately.
  • Manual entry — via the planning dialog, driven by planning_fields["pdu"] entries. The values persist in power_config on Save.

The two are mutually exclusive per placement.

What PDU location means. It is where the power feed enters the rack. A vertical PDU is mounted with its input end towards the feed: with the feed coming up from the floor, the PDU stands with its input at the bottom and bank 1 serves the lower half of the rack; with the feed coming from overhead, the same PDU is mounted upside down, input at the top, and bank 1 serves the upper half. bottom is the default. The builtin mode always assumes bottom; a distribution script such as distribution_example.py reads the value and flips the unit-to-bank mapping for top. Setting it in a design's rack Power dialog stores an override for that design only — the rack's own custom field in DCIM is never changed.

Note pdu_location (top/bottom, for directing which bank claims which units) is a rack-level custom field, not a PDU-level one — it is declared under planning_fields["rack"] (see the example above) and reaches a distribution_script via DesignRackPower merged over rack.cf, the same path as power_limitation. It has nothing to do with power_source_device / power_config, which resolve a PDU's custom fields.

Bank zones, and choosing a feed per device

▶ Video: Part 8 — Bank zones & choosing a feed

Two editor controls sit on top of the distribution result.

Bank zones (a switch next to Power heatmap) draws a narrow strip on the left edge of every face grid: one column per feed leg (a, b, …), showing which U range each PDU bank serves and how full it is, in the same colours as the bank chips. On a rack with several PDUs per leg the leg's PDUs stack in one column, each with its name written up the column at its floor, so it is unambiguous which U to drop a device on to land it on a2 rather than a1. The chip block above the grids uses the same layout — one column per leg, paired PDUs level with each other. The strip is structural, not a colouring view, so it is independent of the heatmap switch.

Per-device feed choice. A device the design adds or moves is attributed to legs automatically — one PSU goes to leg a, two or more to a + b (§2.2 of the spec). To pin one device elsewhere, open its Planning attributes dialog (the tag button on the tile) and use the Power block: one select per PSU, Automatic or a specific leg. The choice is stored on the placement as preferred_feed_legs (a list, one lowercase letter per PSU in PSU order; empty means automatic) and the engine charges those legs instead of the first-N heuristic. Devices the design leaves in place keep their real cabling; the override only steers what is planned. Exposed on the REST/GraphQL placement as preferred_feed_legs.

Planning fields — custom-field bridge (script tier only)

Most sites keep power policy in custom fields: power limitations (rack ceiling), PDU locations (direction), or future site-specific fields. These reach the engine only under distribution_mode = "script" — the "builtin" mode reads no custom fields at all. A distribution_script never hardcodes a site's custom-field names — instead, planning_fields in PLUGINS_CONFIG maps them generically, resolved by name through each entry's source key, so the shipped code never changes per deployment. The rack/PDU planning dialogs' manual cf inputs are therefore a script-tier feature too: with "none" or "builtin", planning_fields has nothing to feed and the dialogs show only native inputs.

"planning_fields": {
    "rack": [
        {"key": "power_limitation", "label": "Power limitation (W)",
         "type": "number", "source": "cf.power_limitation"},
        {"key": "pdu_location", "label": "PDU location", "type": "choice",
         "choices": ["top", "bottom"], "source": "cf.pdu_location"},
    ],
    "pdu": [
        {"key": "pdu_scheme", "label": "Custom PDU scheme",
         "type": "text", "source": "cf.pdu_scheme"},
    ],
}

Each entry declares:

  • key — the name the script/dialog knows it by (e.g., power_limitation).
  • label — what the UI shows.
  • type — number, text, or choice; choice requires choices.
  • source — where to read the value: cf.<fieldname> for custom fields. Dotted paths are self-documenting, matching the naming-template grammar.

The plugin reads from custom fields only (never native fields) and never writes back to dcim. An empty planning_fields (the default) is fine — the base builtin feature needs none. The dialogs then show only native inputs (copy-from-rack, bind-to-feed).

Writing and adapting a script

Copy netbox_rack_design/distribution_example.py and edit the parts that matter to your site: the direction (unit-to-bank mapping if PDU placement is atypical), breaker ceilings (per-bank limits), and redundancy scheme (which PSU lands on which feed for a given device type).

Key points

  • Contract: build(rack, devices) -> Distribution | None. The rack is a real saved dcim.Rack; devices is a normalized list of planned consumers and PDUs. Return the Distribution dict (or None). It's read-only — compute, never write.
  • Config bridge: read custom fields through read_planning_fields(role, obj) — this abstracts the planning_fields map, so a site's rack_power_cap maps to the key power_limitation your algorithm knows. Never hardcode cf names.
  • Shared helpers: both shipped examples reuse distribution._collect_pdus and distribution_example's _unit_to_bank, _legs_for, _charge functions. You are not reinventing the algorithm — you're configuring its behavior.
  • Absolute imports: use from netbox_rack_design.distribution import ... (not relative imports) so the script keeps working if you copy it out of the package into SCRIPTS_ROOT. NetBox's netbox_rack_design package is always importable.

Keeping the script in NetBox's SCRIPTS_ROOT

You can keep the script where NetBox already manages Python: SCRIPTS_ROOT (default <netbox>/scripts/). A file there is importable as scripts.<module>, so reference it as:

"distribution_mode": "script",
"distribution_script": "scripts.power_distribution.build",

Set the config once. Edit configuration.py with the config above and restart NetBox — this is the only step that needs a restart. While the script isn't present yet, the distribution safely falls back to none (per-device heatmap).

After that one-time config change, adding or editing the script itself needs no restart. NetBox picks it up and the plugin imports the build function on the next heatmap render.

Variant 1 — through the UI (Customization → Scripts → Add)

Use this to view and edit the script from the NetBox UI. NetBox lists a module under Scripts only when it contains an extras.scripts.Script subclass, so wrap the example with a tiny one:

from extras.scripts import Script

class PowerDistributionScript(Script):
    class Meta:
        name = "Rack Design power distribution"
    def run(self, data, commit):
        self.log_info("Distribution script for the rack-design editor; nothing to run.")

# ... paste the helpers and build() function from distribution_example.py below ...

Customization → Scripts → Add, name the module power_distribution, and paste the wrapped script. No restart — reopen a design and the new distribution appears immediately. Edit it later the same way.

Variant 2 — copy the file into SCRIPTS_ROOT

If you don't need UI editing, just drop the file in:

cp .../netbox_rack_design/distribution_example.py  $SCRIPTS_ROOT/power_distribution.py

No restart needed; the plugin imports it on the next heatmap render.

Variant 3 — remote script storage (S3 and other STORAGES["scripts"] backends)

When NetBox keeps scripts in remote storage (STORAGES["scripts"] pointing at S3, MinIO or another django-storages backend), a script you add under Customization → Scripts is not on the NetBox server's disk, so a scripts.<module> dotted path cannot import it. Prefix the reference with scriptmodule: instead — the plugin then reads the module through NetBox's script storage, the same way NetBox runs its own scripts:

"distribution_script": "scriptmodule:power_distribution.build",

scriptmodule:<module>.<function> names the file <module>.py at the root of the script storage, i.e. the module name NetBox lists under Scripts. It works with local storage too. The module is cached in each NetBox process: the file is re-read at most every 10 seconds and re-executed only when its content changed, so an edited script takes effect within about 10 seconds, with no restart. A missing module or function falls back to none (per-device heatmap) and the editor shows the red failed notice with the reason.

Referencing the package copy directly, netbox_rack_design.distribution_example.build, also works and needs no copy at all — use that if you only want the shipped defaults and no per-instance editing.

Verify on your instance

A quick end-to-end check that distribution works the way you expect:

  1. Configure and restart. Set distribution_mode in PLUGINS_CONFIG:
"distribution_mode": "builtin",

Restart NetBox so the config is loaded.

  1. Open a rack with PDUs and planned devices. Open a design in the editor and add devices (or view an existing design with devices already placed). Ensure the rack has real or planned PowerFeed records, and each PDU is bound to one.

  2. Toggle the power heatmap. At the top of the editor, find the power (lightning bolt) icon / heatmap toggle. Turn it on. You should see:

  3. Each PDU column labeled with the feed-leg header (A or B).
  4. Inside each PDU, stacked colored banks (green → orange → red by load %).
  5. Device tiles with A/B feed-leg edges (if the device is redundant).
  6. Instant tooltips on hover (used W / breaker W per bank).
  7. Overload warnings in red if any bank exceeds its breaker.

  8. Drag a device to a different rack unit. The bank colors should update to reflect the new load distribution: a device the design moves is charged to the bank at its new U position, even if it still has a real cable to a different outlet — that cabling is assumed to be re-run when the design is implemented. A device you leave alone keeps charging its real outlet's bank.

  9. Check custom fields (script tier only). If you've switched to distribution_mode = "script" with planning_fields configured, add a rack with a power_limitation custom field. Open the Power dialog and verify the field appears as configured. Same for PDU-role fields if your script reads them. (Skip this step under "builtin" — it reads no custom fields.)

Nothing here writes to dcim: distribution only ever runs on the read-only projection, never on page load or on Save.

Switching between modes

  • none → builtin: Restart NetBox. The heatmap now shows per-bank colors instead of per-device.
  • builtin → script: Set distribution_script and restart. The script replaces the built-in; behavior may differ if the script implements customizations.
  • script → none: Set distribution_mode to none and restart. The heatmap reverts to per-device gradient.

A misconfigured or broken script (wrong path, unimportable module, runtime error) degrades to none gracefully — logs a warning, never errors the editor.

Troubleshooting

I see a per-device gradient, not per-bank colors.

  • Check distribution_mode in PLUGINS_CONFIG — if it's "none", that's expected (the default). Set it to "builtin" or "script" and restart.
  • If using "script": check that distribution_script is a valid importable path and the function exists. Enable DEBUG logging to see import/execution errors logged on each heatmap render.

The heatmap looks incomplete; some PDUs are missing.

  • Check that each PDU is bound to a feed (real or planned). A PDU with no binding is omitted from the distribution (logged at debug level).
  • Check that feeds exist: real feeds for a provisioned rack, or planned feeds defined via the Power button for greenfield racks.
  • Check that outlet ports follow the "<bank>/<port>" convention (e.g., 1/1, 2/3). An outlet named pdu-outlet-1 with no / has no bank and is ignored.

The distribution looks wrong; devices are charged to the wrong banks.

  • Check whether the design moves the device. A moved device (a new add, or an existing device dragged to a different unit) is always charged by its new U position — any cabling it still carries is ignored, because that cable is assumed to be re-run when the design is implemented.
  • For a device the design does not move: verify cabling — it should charge the PDU outlet's bank directly (the first segment before /), even if that differs from what its U position would suggest.
  • For a device the design does not move and that has no cabling: verify it's placed at its intended U position. The rack distribution assumes a unit-to-bank mapping based on direction and bank count; a device at U5 might charge a different bank than U7.
  • distribution_mode = "builtin" always splits in a fixed direction (bank 1 at the bottom) — it does not read the rack custom field pdu_location or any other cf.
  • distribution_mode = "script" may read the rack custom field pdu_location ("top" or "bottom") through the planning_fields config bridge to flip the direction (default "bottom" when the field is absent) — check your script and its planning_fields["rack"] entry if the direction is wrong.
  • Inspect the debug logs: logger.debug messages in distribution_example.py / distribution_advanced_example.py trace each device charge and unit mapping.

Warnings or errors appear at the top of the editor.

  • If a warning mentions an overload or power limitation breach, check the specific bank/PDU and device draws. Thresholds (power_warn_pct, power_critical_pct) default to 80% / 100%; override them in PLUGINS_CONFIG or in a custom script.
  • If a warning mentions an unresolvable power_source_device, the planned PDU linked to a real device whose custom fields were requested, but the device was deleted. The distribution falls back to manual power_config fields (or {} if none); no error, just logged.

How do I troubleshoot a custom script?

  • Enable DEBUG logging on the plugin (netbox_rack_design.distribution*). Each heatmap render logs entry, per-device charges, and the final Distribution object.
  • Add logger.debug() calls to your script to trace its own logic.
  • Test in a dev/staging environment first; a broken script degrades the heatmap but never breaks the editor.
  • Restart NetBox once to load a config change (distribution_script path); after that, editing the script file alone needs no restart.

See also

  • PDU distribution specification — the full design reference, feed model details, and Distribution data contract.
  • Device naming — the naming engine, which follows the same configuration patterns (mode selection, built-in, script, config bridge).