Power projection spec

Power projection — specification

Status: draft / active cycle (started 2026-07-13). Authoritative spec for the power feature, in the same spirit as docs/editor-behavior-spec.md. Definition of done = this spec's contracts covered by tests (backend) and the conformance items below verified live.

0. Principle

Power projection is read-only and reflects the planned world — the design applied hypothetically (existing − removes + adds, moves reassigned to their target rack), the same world projection.py already builds. It never writes to dcim. It reuses NetBox's native power primitives where they exist (PowerPort / PowerPortTemplate draw, PowerFeed.available_power, Rack.get_power_utilization) rather than reinventing the electrical model; the plugin's value-add is projecting those numbers onto a not-yet-applied design and distributing them per PDU/bank.

1. Per-device draw (watts)

Resolved per planned device, in order:

  1. Planned add (no real device): sum the device-type's PowerPortTemplate.allocated_draw (fallback maximum_draw).
  2. Existing / moved (real device): sum its PowerPort.allocated_draw (fallback to the type template, then maximum_draw).
  3. Unknown / unaccounted (device HAS power ports, or its type defines port templates, but none carry a draw value): counted as 0 W but flagged — the result carries unknown_draw_count and unknown_devices (their names) so the UI can say which powered devices lack draw data, not silently under-report.
  4. Passive (no power ports at all — patch panels, cable managers, blanking panels): draws nothing by design, so it is neither counted nor flagged (it is not "missing" data). Treated as a known 0 for the heatmap.

2. Three calculation tiers

The tier is chosen by config; each is a strict superset of information over the one before.

Tier 1 — crude, zero-config (default: "тапорно")

No distribution. Per rack:

draw_w      = Σ per-device draw over the planned devices in the rack
capacity_w  = Σ PowerFeed.available_power for the rack's feeds,
              else config `power_capacity_default_w` (fallback)
util_pct    = draw_w / capacity_w * 100
state       = ok | warn | critical      (thresholds below)

Plus a design-level total (Σ racks). This is the always-on baseline — works on a stock instance with nothing modeled beyond device types.

Tier 2 — config-driven distribution across PDUs and feeds/banks

Report utilization per feed/bank, not just per rack. A device's draw lands on the feed(s) its PSUs connect to; a "bank" is a PDU input/phase/breaker group.

Distribution model (by PSU count) — the core rule:

PSUs (PowerPorts) Feeds it touches Per-feed charge
1 the one feed it's cabled/assigned to full device draw on that one feed (single point of failure; never split)
2 (A/B) feed A + feed B full device draw charged to each feed (redundant sizing: either feed must carry it alone on failover)
N its N feeds full draw on each of the redundant feeds it participates in

So a single PSU is never smeared across two feeds — it sits entirely on one. Redundant PSUs charge each feed the full load (worst-case failover), not a split.

Feed assignment source (in order): 1. Real NetBox power cabling where modeled (PowerPortPowerOutletPowerFeed) — authoritative. 2. Config rule for planned/uncabled devices (e.g. alternate A/B by PSU index).

Config sketch:

"power_distribution": {
    "redundancy": "full",          # "full" (each feed sized for whole draw) | "shared"
    "assign": "alternate_ab",      # fallback A/B assignment when no cabling
    # optional per-feed/bank capacity overrides
},

Output: adds a feeds breakdown (per feed: draw_w, capacity_w, util_pct, state) alongside the rack summary. Racks with no distribution config fall back to Tier 1 (rack total only) transparently.

Tier 3 — pluggable power script

Mirrors the naming engine exactly. A config dotted path "power_script": "scripts.power.distribute" points at a read-only callable that receives the planned world (rack + its devices + draws) and returns the distribution (per-PDU/bank allocation, redundancy/phase logic the config table can't express).

  • Same graceful fallback contract as naming: an unresolvable/raising power script logs a warning and falls back to Tier 1 crude, never erroring the page (power is read-only overlay data; a bad script must not break the editor).
  • Same SCRIPTS_ROOT story: the script can live in scripts/ and be edited via the NetBox UI; a shipped generic example demonstrates the contract.

3. Heatmap toggle (the "галка")

A legend/toolbar checkbox "Power heatmap" in the editor (and optionally the read-only elevation view). Default off.

When ON:

  • Normal device styling is neutralized — the state colors (existing / add / move / remove / shadow tints) are suppressed so they don't compete with the heat colors.
  • Every device tile is colored on a green→red gradient by its share of the rack's total draw: share = device_draw / rack_total_draw. Low consumers → green, high consumers → red. (Share is of the rack's total consumption, per the requirement — "от общего кол-ва стойки".)
  • Devices with unknown draw get a distinct neutral shade (e.g. hatched grey), not green — absence of data ≠ zero consumption.
  • A gradient legend replaces/augments the state legend while active.

When OFF: normal styling is restored exactly (the heatmap is a pure view layer over the same tiles — no state change, no dirty flag, nothing saved).

3.1 Design chains

When a design is based on an approved ancestor (docs/design-chains.md), projection is no longer single-layer: capacity_w above (and the per-bank figures in docs/pdu-distribution-spec.md) also count every approved ancestor's planned power feeds and rack-power overrides, resolved by the same all-or-nothing rule (Design.status) the placement replay uses. An ancestor that is not approved, or is implemented, contributes nothing to power either — refused as a whole layer, reported once as a projection conflict, never silently under- or over-counted.

4. Where the numbers come from / surfaces

  • Computed server-side in projection.py, returned as a power block on the projection bundle so both the editor and the read-only elevation view read the same numbers.
  • v1 recompute cadence: on load and after Save (no mid-drag live recompute). The heatmap uses the last computed bundle; a later phase may recompute live.

5. Out of scope (v1)

  • Live mid-drag power recompute.
  • Breaker-trip / inrush / power-factor modeling beyond NetBox's own fields.
  • Automatic A/B redundancy inference without config or script (Tier 3 can do it).

6. Implementation phases (test-first, one at a time)

  • A. Backend Tier 1 — per-device draw resolution + per-rack/design crude projection in projection.py, power bundle block, unknown_draw_count. Backend tests: draw resolution (add-via-template, existing-via-port, unknown→0+flag), per-rack sum, thresholds, design total, removes/moves reflected, feed-vs-config capacity, read-only (no dcim writes).
  • B. Heatmap toggle — editor checkbox, style neutralization, green→red gradient by rack share, unknown shade, gradient legend, off-restores-exactly. e2e tests.
  • C. Tier 2 — config-driven PDU/bank distribution + per-PDU/bank output + tests.
  • D. Tier 3power_script loader with graceful Tier-1 fallback (reuse the naming loader pattern) + shipped generic example + docs + tests.

7. Conformance checklist (definition of done)

  • [ ] Tier 1 works with nothing configured; capacity uses feeds when present.
  • [ ] Planned adds/removes/moves change the projected numbers correctly.
  • [ ] Unknown-draw devices are flagged, not silently zero.
  • [ ] Heatmap on: state styling suppressed, tiles gradient-colored by rack share, unknown shade distinct, legend shown.
  • [ ] Heatmap off: original rendering byte-identical to before toggling.
  • [ ] Power is read-only: no dcim writes, no design dirty flag from the overlay.
  • [ ] Bad power_script falls back to Tier 1 (page never errors).